Perdue School of Business Chilled Water

Salisbury University — Salisbury, Maryland

Perdue School of Business

Improved efficiency of the chilled water system at the new Perdue School of Business at Salisbury University through the use of PIC‑V® and MVP™ pressure independent control valves.

112,800 ft² Total facility square footage
20°F Average chilled water ΔT achieved (vs. 16°F design)
+20% Higher ΔT than designed — exceeded every projection
LEED® Gold certification targeted

Project Overview

Project Salisbury University — Perdue School of Business
Application Chilled Water AHU & Fan Coil Cooling Coils
Products Used PIC‑V® & MVP™ Pressure Independent Control Valves
Design Engineer Todd Garing, PE — Mueller Associates
Griswold Representative Hydro Tec / Green Shoots Controls — Brad Walker

The Facility

This project included construction of the new Perdue School of Business and supporting infrastructure for Salisbury University. The facility provides approximately 112,800 square feet of classroom, assembly, lab, administrative, and general use areas to support current and projected undergraduate, graduate, and executive education programs. The project was designed to achieve LEED® Green Building Gold certification.

Chilled Water Plant

The chilled water system is variable primary flow, consisting of two 150-ton McQuay magnetic bearing variable speed chillers operating at a 50/50 load split, two cooling towers with variable speed fans, two redundant variable speed chilled water distribution pumps, and three condenser water pumps (one as a common backup). The system serves various air handling unit (AHU) and fan coil unit cooling coils, with AHU chilled water flow controlled by Griswold Controls PIC‑V® and MVP™ pressure independent control valves.

Air Distribution Systems

The air distribution system consists of five Variable Volume AHUs with zone reheat coils and one Single Zone Variable Volume AHU. AHUs 1, 4, 5, and 6 serve classrooms, offices, and general areas — each equipped with variable volume static pressure controlled supply fans, volumetric return fan tracking, energy recovery wheels, preheat coils, chilled water coils, air side economizers, and demand controlled ventilation. AHU-2 serves the auditorium exclusively, with a variable volume temperature controlled supply fan, preheat coil, chilled water coil, reheat coil, air side economizer, and demand controlled ventilation.

System Performance Analysis

Tim Jones, the resident operations engineer for the University, provided systems data collected through the Building Automation System (BAS). Load profiles were examined for over a year at conditions from 20% through 100% chiller capacity.

“This system meets our most demanding needs for efficiency and performance.”

— Tim Jones, Resident Operations Engineer, Salisbury University (manages 22 buildings)

These observations are supported by the chilled water system’s actual temperature difference being more than 20% higher than the design of 16°F ΔT. The chilled water system operates at an average 20°F ΔT — reducing the design flow rate from 1.5 gpm/ton (16°F) to 1.20 gpm/ton (20°F). Every metric that was analyzed exceeded projections.

Key performance outcomes:
  • Average ΔT of 20°F Exceeded the design ΔT of 16°F by more than 20% — at every load condition from startup to full load.
  • Reduced flow rate Design flow reduced from 1.5 gpm/ton to 1.20 gpm/ton — directly reducing pumping energy.
  • Stable AHU fan speeds Precise load tracking control kept supply air fan VFD speeds consistent and efficient across all AHUs.
  • Consistent ΔT stability Temperature difference remained stable through varied AHU supply airflow and chiller capacity conditions.
  • Proven under peak load System performance confirmed even on a humid 90°F day — as shown in the onboard chiller screens (Appendix A).

“We specified pressure independent control valves and designed for a high chilled water temperature difference to improve energy efficiency and reduce pumping energy specifically. The gathered data supports the performance of the system to deliver consistently high temperature differential at varied load conditions.”

— Todd Garing, PE, Mueller Associates (Design Engineer)

Questions about this application? Contact info@GriswoldControls.com or 949.559.6000

This case study was coordinated by the Griswold Controls representative in Maryland in conjunction with Oscar Walker of Green Shoots Controls.

Griswold Controls Representative — Hydro Tec

Brad Walker — (410) 404-6647

bwalker@hydrotecinc.com

greenshootscontrols.net

Appendix A — Chiller Screen Data

Onboard chiller screens recorded during the case study, including readings captured on a humid 90°F day. Screens are typical of system performance throughout the study period.

Perdue School of Business Chilled Water – Appendix A1 Perdue School of Business Chilled Water – Appendix A2 Perdue School of Business Chilled Water – Appendix A3 Perdue School of Business Chilled Water – Appendix A4

Appendix B — BAS Performance Graphs

Graph Terms CWGPM% – Chilled Water GPM Percentage  |  CWSY ΔT – Chilled Water System Delta T  |  Chiller Capacity % – Chiller Capacity Percentage  |  OATF – Outside Air Temperature Fahrenheit  |  OATH% – Outside Air Temperature Humidity Percent  |  SAF VFD Avg % – Supply Air Fan VFD Average Percent  |  LAT WB-F – Latent Air Temperature Wet Bulb Fahrenheit
Perdue BAS Performance Graph B1 Perdue BAS Performance Graph B2 Perdue BAS Performance Graph B3 Perdue BAS Performance Graph B4 Perdue BAS Performance Graph B5 Perdue BAS Performance Graph B6 Perdue BAS Performance Graph B7 Perdue BAS Performance Graph B8
Griswold Controls Case Studies

Have a question about this or another Griswold Controls Case Study?

Fill out the form below and someone from Griswold Controls will get back to you shortly.


    Please prove you are human by selecting the flag.

    Zoomed Image